Instrument Transformer

High Voltage Current Transformers

Fibre & Fibre Glass Products designs and manufactures Current and Potential Transformers in its unit in Vadodara. Fibre & Fibre has facility of in-house fabrication, Painting and Testing.

FIBRE AND FIBRE GLASS PRODUCTS, DESIGNS THE TRANSFORMERS AS PER CUSTOMER REQUIREMENTS

Application :

Role of Current Transformers in electrical systems is of prime importance as they are the means of stepping down current to measurable values. Secondary current is of proportionately lower value to the primary current. Current Transformers can thus be used with ammeters for the measurements of current and with relays for protection of electrical instruments.

Basic Feature :

  • To reduce primary current and voltage to a measurable value
  • To protect electrical systems with the help of relays
  • To reduce risk to humans by isolating measuring side from high Current / Voltage side.

Design Criterion

Current Transformer is manufactured in Live-Tank or Dead- Tank design as per customer specification. In Live –Tank design the secondary winding is insulated with multiple layers of high quality pre-dried insulating paper. The complete job lies in upper tank that is on system voltage. Whereas in Dead-Tank design the primary is insulated with multiple layers of high quality pre dried insulating paper. In this case complete job lies in dead tank that is on earth potential.

Semi conducting paper is used to make a capacitor layers to control discharge. The CT is designed to meet specified thermal and dynamic short circuit currents.

The secondary winding consists of core made from CRGO (Cold Rolled Grain Oriented). Super enameled copper wire is uniformly wound on core with the help of toroid winding machines.

The transformer is dried and filled with filtered transformer oil under Vacuum. A tan-delta value of 0.005 or less can be achieved. The transformer can be removed from the Vacuum Impregnation Plant after achieving the required value for tan-delta.

Nitrogen gas is filled above the oil to hermetically seal the transformer from the outside.

The metal parts can be painted or galvanized as per customer requirement/specification. All fasteners used are Hot-dip galvanized. Stainless steel fasteners can be used on request.

 132-KV-Potential-Transformer 132 KV Dead Tank Current Transormer
ELECTRICAL CHARACTERISTICS OF CURRENT TRANSFORMERS
(CONFIRMING TO IS: 2705 & IEC: 60044-1)
TYPE: OUTDOOR, OIL COOLED
Nominal System Voltage (kv) 132
Highest System Voltage (kv) 145
Power Frequency withstand voltage 1 Min (kv) 275
Impulse withstand Voltage (kvp) 650
Rated Burden 2.5 VA TO 40 VA
Rated Frequency (Hz) 50 Hz
Creepage Distance Phase to Earth (m.m.) 3625
Rated Primary Current (Amp.) 5 Amp. to 2000 Amp.
Rated Continuous Thermal Current (Amp.) Max 125% of rated primary current
Rated Secondary Current (Amp.) 1 Amp. To 5 Amp. (or as per customer requirement)
Rated Short Time Thermal Current 3KA TO 40KA for one/three second
Rated Dynamic Current (KA-Peak) 2.5 times of short time current.
Accurate Class (IS/IEC Standard) 0.2s (Min.) for Metering & 5P, 10P & PS for Protection
Rated Instrument Security Factor 5
Rated Accuracy Limit Factor 10, 20, 30
 132-KV-Potential-Transformer 132 KV Live Tank Current Transormer
APPROXIMATE OVER ALL DIMENSIONS OF EHV GRADE CURRENT
TRANSFORMERS (MFG. BY FFGP)
132 KV LIVE TANK TOTAL HEIGHT (m.m.) 2200 m.m.
TOTAL WIDTH (m.m.) 680 m.m.
TOTAL DEPTH (m.m.) 500 m.m.
OIL QTY. (Ltr.) 110 Ltr. (Approx)
TOTAL WEIGHT (Kgs.) 400 Kgs. (Approx)
132 KV DEAD TANK. TOTAL HEIGHT (m.m.) 2600 m.m.
TOTAL WIDTH (m.m.) 900 m.m.
TOTAL DEPTH (m.m.) 580 m.m.
OIL QTY. (Ltr.) 150 Ltr. (Approx)
TOTAL WEIGHT (Kgs.) 450 Kgs. (Approx)